EOCR Motor Protection Relay With 3 Integral CT Screw Terminal, Separate Display, Range: 0.5-60A, Output: 1NO (AL/UL/TO) 1NC+1NO (OL), Supply: AC/DC100-240V, Panel/Din-Rail/Flush Mount
General Characteristics
Device short name: EOCR-FDM2
Product or component type: Protection relay
Protection type: Sensitivity to phase reverse, Phase unbalance (10...50 %), Sensitivity to phase loss, Locked rotor for running (In > 1.5...5 times OC setting), Locked rotor for starting (In > 2...8 times OC setting), Underload (In < UC setting), Overload (In > OC setting)
Product specific application: Motor protection
Network type: AC
Network frequency: 50...60 Hz
Protection adjustment range: 0.5...60 A
Tripping threshold: 0.5...60 A (definite), 0.5...32 A (inverse and thermal)