Carlo Gavazzi Energy Management Smart Power Analyzer Types WM30-96 Modular Base Module, 4x4 Digits LCD 96x96mm Panel Mount, Range: 400/690VAC 1(2)A, 1/2/3 Phase, Supply: 18-60VAC/VDC
Three-phase smart power analyzer with built-in advanced configuration system and LCD data displaying. Particularly recommended for the measurement of the main electrical variables. WM30 is based on a modular housing for panel mounting with IP65 (front) protection degree. Moreover, the analyzer can be provided with digital outputs that can be either for pulse proportional to the active and reactive energy being measured or/and for alarm outputs. The instrument can be equipped with the following modules: RS485/RS232, Ethernet, BACnet-IP or BACnet MS/TP communication ports, pulse and alarm outputs.
General Characteristics
Class 0.5 (kWh) according to EN62053-22
Class C (kWh) according to EN50470-3
Class 2 (kvarh) according to EN62053-23
Accuracy ±0.2% RDG (current/voltage)
Instantaneous variables readout: 4x4 DGT
Energies readout: 9+1 DGT
System variables: VLL, VLN, A, VA, W, var, PF, Hz, Phase-sequence-asymmetry-loss.
Single phase variables: VLL, VLN, AL, An (calculated), VA, W, var, PF
Both system and single phase variables with average and max calculation
Harmonic analysis (FFT) up to the 32nd harmonic (current and voltage)
Energy measurements (imported/exported): total and partial kWh and kvarh
Energy measurements according to ANSI C12.20 CA 0.5, ANSI C12.1 (revenue grade)
Run hours counter (8+2 DGT)
Real time clock function
Application adaptable display and programming procedure (Easyprog function)
Universal power supply: 18 to 60VAC/DC, 90 to 260AC/VDC
Front dimensions: 96x96 mm
Front protection degree: IP65, NEMA4X, NEMA12
One RS232 or RS485 port (on request)
Communication protocol: MODBUS-RTU, iFIX SCADA compatibility
MODBUS TCP/IP Ethernet port (on request)
BACnet-IP over Ethernet port (on request)
BACnet MS/TP over RS485 (on request)
Up to 2 digital outputs (pulse, alarm, remote control) (on request)
Up to 4 freely configurable virtual alarms
Up to 2 analogue outputs (+20mA, +10VDC) (on request)